If you service fire protection systems in hospitals, you need to know which accreditation body your client answers to — because the report format requirements are different, the survey frequency is different, and the consequences of getting it wrong are real.

The two dominant hospital accreditation organizations in the United States are the Joint Commission and DNV. Together they account for the vast majority of accredited hospitals. This article explains what makes them different from a fire inspector's perspective.

The Basics

The Joint Commission

The largest hospital accreditor in the US. Accredits hospitals, behavioral health facilities, home health agencies, nursing homes, and labs. Surveys occur every three years and are unannounced. Uses EC (Environment of Care) standards with EP (Elements of Performance) codes.

DNV (Det Norske Veritas)

The second largest hospital accreditor, accrediting approximately 600 US hospitals. Focuses primarily on hospitals and larger healthcare systems. Surveys occur annually and are unannounced. Uses NIAHO (National Integrated Accreditation for Healthcare Organizations) standards with SR (Standard Requirements) codes.

Both organizations are approved by CMS (Centers for Medicare and Medicaid Services) to deem hospitals in compliance with Conditions of Participation — the federal requirements for facilities that receive Medicare and Medicaid funding. Both require NFPA code compliance. But the way they organize and verify that compliance — and the report format they expect — differs significantly.

The Key Differences for Fire Inspectors

FactorJoint CommissionDNV
Survey frequencyEvery 3 years (unannounced)Annually (unannounced)
Report format standardEC.02.03.05 with EP codesNIAHO PE.2 with SR codes
Code reference systemEC codes (e.g., EC.02.03.05 EP 4)SR codes (e.g., PE.2, SR.10)
NFPA alignmentNFPA 101, 72, 25, 10, 110NFPA 101, 72, 25, 10, 99 (storage), 110
Report organizationOrganized by EC standard and EPCover sheet, summary, results, signature — no EP codes
Number of accredited hospitals~4,000+~600
Self-assessment requirementAnnual self-assessment between surveysISO 9001 quality management integration

Report Format: Where It Gets Practical

The most immediately practical difference for an inspection contractor is the report format. Here's what each requires:

Joint Commission report format

A Joint Commission-compliant fire inspection report organizes results by EC standard. For a NFPA 72 inspection, the relevant standard is EC.02.03.05 — and each checklist item must be mapped to its specific EP code. The report must show, for each EP, how many devices passed, failed, or were N/A, and the overall compliance status for that EP.

A standard NFPA 72 inspection report — organized by device type or location — does not satisfy Joint Commission requirements without reformatting. The inspector who delivers an unformatted report to a Joint Commission-accredited facility creates compliance risk for the facility and credibility risk for themselves.

DNV / NIAHO report format

A DNV-compliant report does not use EC codes. Instead it references NIAHO SR codes — specifically PE.2, SR.10 for fire protection system inspection, testing, and maintenance. The structure is simpler: cover sheet, compliance summary, inspection results by system, signature page.

The absence of EP codes actually makes the DNV format somewhat easier to produce — but it still requires intentional formatting. A generic NFPA 72 report without NIAHO references doesn't satisfy DNV requirements either.

Survey Frequency and Its Implications

DNV's annual survey cycle has a significant practical implication: there's no three-year window in which a hospital can let its documentation lapse and catch up before the next survey. Every year, the records need to be complete and current.

For the inspection contractor servicing a DNV-accredited hospital, this means the annual inspection report needs to be delivered promptly — not weeks later — and deficiencies need to be tracked and followed up proactively. A facility with an active DNV survey cycle has less tolerance for documentation gaps than a Joint Commission facility with two more years before their next survey.

How to find out which body accredits a facility: Ask the facilities director or safety officer directly. Both organizations publish lists of accredited facilities — Joint Commission on qualitycheck.org, DNV on their hospital search tool. If you're bidding on a new healthcare contract, knowing the accreditation body before the bid lets you specify the correct report format in your proposal — a differentiator most competitors miss.

NFPA 99 — The DNV Difference

One standard DNV references more explicitly than Joint Commission is NFPA 99, the Health Care Facilities Code. DNV NIAHO standards lean on NFPA 99 for how medical gases are stored and handled — how oxygen and other cylinders are separated, secured, and signed, and how liquid-oxygen and gas-equipment storage areas are kept clear of ignition sources. Fire Inspect Hub covers that slice directly: the NFPA 99 Chapter 11 inspection for medical-gas cylinder and container storage — fire separation, oxidizer separation, securing and signage, and liquid-oxygen storage — so when a DNV survey turns to medical-gas storage, the inspection and the record already sit in the same platform as your NFPA 72 and NFPA 25 work.

To be clear on scope: this is the storage and handling side of NFPA 99 (Chapter 11). It is not piped medical-gas system verification or ASSE 6030 certified-verifier work — that's a separate qualification handled by a medical-gas verifier. Fire Inspect Hub documents the storage conditions a fire inspector is there to assess.

What This Means for Your Software

Fire inspection software that supports only one accreditation format — or neither — creates extra work for every healthcare inspection. The right platform generates the appropriate report format based on what the facility needs: standard NFPA format for non-accredited buildings, EC.02.03.05 format for Joint Commission hospitals, and NIAHO PE.2 format for DNV hospitals. Same inspection data, three output formats, zero manual reformatting.

Fire Inspect Hub supports Joint Commission, DNV, and standard report formats.

Complete one inspection. Select the report format at review. Generate the right output for any healthcare client.